Vermont Castings Vigilant II 2310 Instructions d'exploitation Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
12
Vermont Castings Vigilant
®
2000898
An unprotected mantel must have a minimum clear-
ance of 36”, measured from the stove’s top plate; with a
ventilated shield the clearance may safely be reduced
to 18”.
Unprotected top trim must be a minimum of 36” from
the stove’s top surface; with a ventilated trim shield the
clearance may be safely reduced to 18”.
Unprotected side trim which protrudes 2” or more from
the face of the replace must have a minimum 36” of
clearance, measured from the stove’s top side edge;
with a ventilated trim shield, the clearance may be
safely reduced to 18”.
Unprotected side trim which protrudes less than 2” from
the replace face must have a minimum clearance of
18”; with a ventilated trim shield, this may be safely
reduced to 12”. (Fig. 15)
ST691
Vigilant
trim clearances
8/7/01 djt
C C
A
B
 
A. Mantel .... 36” (910mm) 18” (460mm)
B. Top Trim . 36” (910mm) 18” (460mm)
C. Side Trim
.......Over 2” 36” (910mm) 18” (460mm)
.....Under 2” 18” (460mm) 12” (300mm)
ST691
 Maintain clearances to combustible mantel compo-
nents.

Whenever possible, design your installation so that the
chimney connector does not pass through a combus-
tible wall. If you are considering a wall-pass through in
your installation, be sure you check with your building
inspector before you begin. Also check with the chim-
ney connector manufacturer for any specic require-
ments.
Accessories are available on the market which have
been tested and listed specically for use as wall pass-
throughs. Use only these tested and listed accessories
for wall pass-throughs.
The National Fire Protection Association (NFPA) has
established guidelines for passing chimney connectors
through combustible walls. Many building code inspec-
tors follow these guidelines when approving installa-
tions.
The illustration below shows one NFPA recommended
method, in which all combustible material in the wall
is cut away from the single wall connector a sufcient
distance to provide the required 12” clearance for the
connector. Any material used to close up the opening
must be noncombustible.
D
E
F
I
A
N
T
ST493
Brick pass thru
11/00
Wall Stud
Chimney Con-
nector
Floor Pro-
tection
12”
Noncombustible
Naterial
ST493
 An approved wall pass-through method.
Three other methods are also approved by the NFPA.
•Using a section of double-wall chimney with a nine-
inch clearance to combustibles
•Placing a chimney connector pipe inside a ventilated
thimble, which is then separated from combustibles by
six inches of berglass insulating material
•Placing a chimney connector pipe inside a section of
eight-inch diameter solid insulated factory-built chim-
ney, with two inches of airspace between the chimney
section and combustibles.

The chimney connector should be made of 24 gauge
or heavier sheetmetal. Galvanized chimney connector
should not be used, as it may release toxic fumes when
exposed to high temperatures.
The chimney connector should be as short and direct
as possible, with no more than two 90 degree turns.
Vue de la page 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 27 28

Commentaires sur ces manuels

Pas de commentaire